    55kw 75hp 220v 380v VFD Variable Frequency Drive Optimal V/F Mode

    Ask Lasest Price
    Brand Name : VEIKONG
    Model Number : VFD500-055G/075GT4B
    Certification : CE, ROHS
    Price : Please contact quotation
    Payment Terms : T/T, Western Union, L/C
    Supply Ability : 1000 units per week
    Delivery Time : depends on quantities
    • Product Details
    • Company Profile

    55kw 75hp 220v 380v VFD Variable Frequency Drive Optimal V/F Mode

    55kw 75hp 220v 380v vector control inverters frequency drive ac drive


    Performance Advantage


    Advanced motor control algorithm


    High performance open loop vector control


    Optimal V/F mode


    Excellent ramp slope control


    Fast auto-tune (less than 1 minute)


    Overload: 150% rated output current, 1 minute


    Low frequency torque: 0.5Hz: 100% rated torque 1Hz: 150% rated torque


    ItemSpecifiation
    InputInuput Voltage

    1phase/3phase 220V:200V~240V

    3 phase 380V-480V:380V~480V

    Allowed Voltage fluctuation range-15%~10%
    Input frequency50Hz / 60Hz,fluctuation less than 5%
    OutputOutput Voltage3phase:0~input voltage
    Overload capacity

    General purpose application:60S for 150% of the rated current

    Light load application:60S for 120% of the rated current

    ControlControl mode

    V/f control

    Sensorless flux vector control without PG card(SVC)

    Sensor speed flux vector control with PG card (VC)

    Operating modeSpeed control,Torque control(SVC and VC)
    Speed range

    1:100 (V/f)

    1:200( SVC)

    1:1000 (VC)

    Speed control accuracy

    ±0.5% (V/f)

    ±0.2% (SVC)

    ±0.02% (VC)

    Speed response

    5Hz(V/f)

    20Hz(SVC)

    50Hz(VC)

    frequency range

    0.00~600.00Hz(V/f)

    0.00~200.00Hz(SVC)

    0.00~400.00Hz(VC)

    Input frequency resolution

    Digital setting: 0.01 Hz

    Analog setting: maximum frequency x 0.1%

    Startup torque

    150%/0.5Hz(V/f)

    180%/0.25Hz(SVC)

    200%/0Hz(VC)

    Torque control accuracy

    SVC:within 5Hz10%,above 5Hz5%

    VC:3.0%

    V/f curve

    V / f curve type: straight line, multipoint, power function, V / f separation;

    Torque boost support: Automatic torque boost (factory setting), manual torque boost

    Frequency giving ramp

    Support linear and S curve acceleration and deceleration;

    4 groups of acceleration and deceleration time, setting range 0.00s ~ 60000s

    DC bus voltage control

    Overvoltage stall control: limit the power generation of the motor by adjusting the output frequency to avoid skipping the voltage fault;


    Undervoltage stall control: control the power consumption of the motor by adjusting the output frequency to avoid yaw failure


    VdcMax Control: Limit the amount of power generated by the motor by adjusting the output frequency to avoid over-voltage trip;

    VdcMin control: Control the power consumption of the motor by adjusting the output frequency, to avoid jump undervoltage fault

    Carrier frequency1kHz~12kHz(Varies depending on the type)
    Startup method

    Direct start (can be superimposed DC brake); speed tracking start


    Replace famous brands vfd in general application.


    Failure and diagnosis


    The VFD500 inverter has perfect protection. If a fault occurs, the inverter will act according to the fault attribute. For more serious faults, the inverter will directly block the output; for general faults, it can be configured to stop or continue to operate according to the scheduled stop mode. After the inverter fails, the fault relay contacts act and the fault code is displayed on the display panel. Before seeking service, users can perform self-checking according to the tips in this section, analyze the cause of the fault, and find a solution.


    Fault NameFault codeDisplayPossible CausesSolutions

    Inverter unit

    protection

    1Er. SC

    1: motor insulation aging

    2: the cable is damaged and contact, short circuit

    3:The distance between motor and inverter are too long.

    4: output transistor breakdown

    5: the internal wiring of the inverter is loose, or the hardware is bad.

    6:brake transistor short circuit

    1. Confirm the insulation resistance of the motor. If it is turned on, replace the motor.

    2. Check the power cable of the motor

    3. Install reactor or output filter

    4, seeking technical support

    5, seeking technical support

    6. Check if the braking resistor is damaged and the wiring is correct.

    Over current

    during

    acceleration

    2Er.OC1

    1: The output circuit is grounded or

    short circuited.

    2: Motor auto-tuning is not performed.

    3: The acceleration time is too short.

    4: Manual torque boost or V/F curve is

    not appropriate.

    5: The voltage is too low.

    6: The startup operation is performed

    on the rotating motor.

    7: A sudden load is added during

    acceleration.

    8: The frequency inverter model is of

    too small power class.

    1: Eliminate external faults.

    2: Perform the motor auto-

    Tuning in cold state

    3: Increase the acceleration

    time.

    4: Adjust the manual torque

    boost or V/F curve.

    5: Adjust the voltage to normal

    range.

    6: Select rotational speed

    tracking restart or start the

    motor after it stops.

    7: Remove the added load.

    8: Select a frequency inverter

    Of higher power class.

    Over current

    during

    deceleration

    3Er.OC2

    1: The output circuit is grounded or

    short circuited.

    2: Motor auto-tuning is not performed.

    3: The deceleration time is too short.

    4: The voltage is too low.

    5: A sudden load is added during

    deceleration.

    6: The braking unit and braking

    resistor are not installed

    1: Eliminate external faults.

    2: Perform the motor

    auto-tuning.

    3: Increase the deceleration time.

    4: Adjust the voltage to normal

    range.

    5: Remove the added load.

    6: Install the braking unit

    And braking resistor.

    Over current

    at constant

    speed

    4Er.OC3

    1: The output circuit is grounded or

    short circuited.

    2: Motor auto-tuning is notperformed.

    3: The voltage is too low.

    4: A sudden load is added during

    operation.

    5: The frequency inverter model is of

    too small power class.

    1:Eliminate external faults.

    2: Perform the motor auto-tuning.

    3:Adjust The voltage to normal range.

    4: Remove the addedload.

    5: Select a frequency

    Inverter of higher power class.

    Overvoltage

    during

    acceleration

    5Er.OU1

    1:the input voltage is too high

    2:The surge voltage is mixed in the input power supply.

    3: there is an external force to drive the motor to run, or the brake type load is too heavy

    4:the acceleration time is too short

    5:the motor is shorted to ground

    1:the power supply voltage is reduced to the normal range

    2:install DC reactor

    3:Cancel the external force of the draggable motor or install the brake unit

    4: increase the acceleration time

    5:eliminate the part of the ground short circuit


    Overvoltage

    during

    deceleration

    6Er.OU2

    1:the input voltage is too high

    2:The surge voltage is mixed in the input power supply.

    3: there is an external force to drive the motor to run, or the brake type load is too heavy

    4:the decceleration time is too short

    5:the motor is shorted to ground

    1:the power supply voltage is reduced to the normal range

    2:install DC reactor

    3:Cancel the external force of the draggable motor or install the brake unit

    4: increase the decceleration time

    5:eliminate the part of the ground

    Overvoltage

    at constant

    speed

    7Er.OU3

    1:the input voltage is too high

    2:The surge voltage is mixed in the input power supply.

    3: there is an external force to drive the motor to run, or the brake type load is too heavy

    4:the acceleration or decceleration time is too short

    5:the motor is shorted to ground

    1:the power supply voltage is reduced to the normal range

    2:install DC reactor

    3:Cancel the external force of the draggable motor or install the brake unit

    4: increase the acceleration or decceleration time

    5:eliminate the part of the ground

    Low voltage8Er.Lv1

    1: Instantaneous power failure occurs

    on the input power supply or input phase loss

    2: The frequency inverter's input

    voltage is not within the allowable

    range.

    3: cut off the power during operation

    4:the internal wiring of the inverter is loose, or the hardware is bad.

    1:Check if the input power supply is abnormal, whether the input power terminal is loose, whether the input contactor or the air switch is abnormal.

    2:adjust the voltage to the normal range

    3:Power off after the inverter stops

    4:seeking technical support

    5: For the unstable power supply, if the performance requirements are low, try to enable the undervoltage stall function (P23.00).

    Contactor open9Er.Lv2

    1: Instantaneous power failure occurs

    on the input power supply

    2: The frequency inverter's input

    voltage is not within the allowable

    range.

    3: cut off the power during operation

    4:the internal wiring of the inverter is loose, or the hardware is bad.

    1:Check if the input power supply is abnormal, whether the input power terminal is loose, whether the input contactor or the air switch is abnormal.

    2:adjust the voltage to the normal range

    3:Power off after the inverter stops

    4:seeking technical support

    5: For the unstable power supply, if the performance requirements are low, try to enable the undervoltage stall function (P23.00).

    Frequency

    inverter

    overload

    10Er. oL

    1:The load is too large or the motor is blocked.

    2:the large inertia load acceleration and deceleration time is too short

    3: When the VF is controlled, the torque boost or V/F curve is not suitable.

    4:the frequency converter selection is too small

    5:overload at low speed operation

    1. Reduce the load and check the motor and mechanical conditions.

    2, increase the acceleration and deceleration time

    3. Adjust the torque boost or V/F curve

    4, select the inverter with a larger power level

    5. Perform motor self-learning in cold state and reduce carrier frequency at low speed

    Motor

    overload

    11Er.oL1

    1:The load is too large or the motor is blocked.

    2:the large inertia load acceleration and deceleration time is too short

    3:When the VF is controlled, the torque boost or V/F curve is not suitable.

    4:the motor selection is too small

    5:overload at low speed operation

    6:Improper setting of motor parameters and motor protection parameters

    1. Reduce the load and check the motor and mechanical conditions. Correctly set the motor parameters and motor protection parameters.

    2, increase the acceleration and deceleration time

    3. Adjust the torque boost or V/F curve

    4, select a motor with a higher power level

    5. Perform motor self-learning in cold state and reduce carrier frequency at low speed

    6, check the settings of related parameters